Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)1 No No Clear the entrance to the machine room. Access to the machine space shall maintained in a clear and unobstructed manner. 5/8/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Exhaust fan is missing cover in machine room. Replace the fan cover. 5/8/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Up to date operating certificate is required in the machine room. 5/8/2023
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Guard machine room light. 5/8/2023
conversion conversion n/a No No Remove emergency lights in car 10/24/2018
conversion conversion n/a No No Remove oil from pit floor 10/24/2018
conversion conversion n/a No No Remove oil from pit floor 10/24/2018
conversion conversion n/a No No Repair emergency light in car 10/24/2018
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door shall be self-closing and self-locking. 4/20/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 4/20/2026
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Fire service testing shall be documented monthy. 4/20/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Front door close button does not work. 4/20/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Need a maintenance control program on site posted on controller asap 11/3/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room shall be self-closing and self-locking
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No No MO State operating certificate in the machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) Yes No Stop switch shall be wired to alarm for audible notification
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No The emergency phone shall be operational and code compliant. The answering service can not be heard. 12/29/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. Yes No Cab lighting shall be a dedicated circuit
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No Repair Phase 2 Fire Service in car on hold will not over ride door close button 4/15/2019
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 (Re-Inspection) Yes No Packing on jack is leaking. Take corrective action as needed. 3/28/2023
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Fire service phase 1 is working, but will not transfer to phase 2. Take corrective action as needed. 3/28/2023
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 (Re-Inspection) Yes No Packing on jack is leaking. Take corrective action as needed. 5/8/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Two-way communications device shall work. 4/20/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Stop switch shall be wired to alarm for audible notification (after 1984). Front COP stop does not sound alarm. 4/20/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) Yes No Car door restrictor shall work at all floors. Multiple brackets missing. 4/20/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. Yes No Cab lighting shall be a dedicated circuit. Currently on the same circuit as second floor hallway lighting/receptacles. NEC 620-22 4/20/2026