Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No No MO State operating certificate in the machine room.
MO Minimum : Elevators (G)2-Alterations 8.7.2.14.2 Car Enclosure Yes No Emergency light and bell not working 8/27/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Need a maintenance control program on site posted on controller asap 11/3/2021
MO Minimum : Elevators (I) - Pits (I)1 No No Remove oil from the pit floor. The pit shall be kept clean and dry. 12/4/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No The emergency phone shall be operational and code compliant. The answering service can not be heard. 12/29/2022
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 (Re-Inspection) Yes No Packing on jack is leaking. Take corrective action as needed. 5/8/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Fire panels on wall in machine room. Only elevator related equipment is allowed. 6/5/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Up to date operating certificate is required in the machine room. 6/5/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Remove fire panels on the wall in the machine room. Machine room shall only have equipment related to the operation of the elevator. 6/5/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Up to date operating certificate is required in the machine room. 6/5/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Two-way communication device shall work. 4/20/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. Yes No Fire panels located on the wall in the machine room. Only elevator related equipment allowed. Cited multiple years. 4/20/2026
MO Minimum : Elevators (H) - Machine Rooms (H)8 No No Outlet in machine room needs to have a cover installed. 4/20/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 4/20/2026
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Fire service testing shall be documented monthly. 4/20/2026