Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a The fireman's service key switch bezel is unreadable and shall be replaced. 7/23/2018
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x The governor rope is rouged and nearing the minimum diameter. The governor rope shall be replaced within 45 days of the annual inspection. 5/25/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The pit lighting shall be operational.
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x x The governor rope is bad and shall be replaced. Elevator Red Tagged.