MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
The pit lighting shall be operational.
|
|
conversion
|
conversion
|
n/a
|
|
|
The fireman's service key switch bezel is unreadable and shall be replaced.
|
7/23/2018
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
x
|
The governor rope is bad and shall be replaced. Elevator Red Tagged.
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
The governor rope is rouged and nearing the minimum diameter. The governor rope shall be replaced within 45 days of the annual inspection.
|
5/25/2021
|