conversion
|
conversion
|
n/a
|
|
|
The fireman's service key switch bezel in the lobby is unreadable and shall be replaced.
|
7/23/2018
|
conversion
|
conversion
|
n/a
|
|
|
The fireman's service key switch bezel in the car is unreadable and shall be replaced.
|
7/23/2018
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
The emergency phone is not audible from inside the car due to extremely low volume. The emergency phone shall be repaired.
|
5/25/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
|