Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 9/21/2021
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes The doors shall not close automatically on phase two fire service. The unit wasn't red tagged because it is the only elevator in the building. Re-inspection required in 14 days. 11/16/2022
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Yes No Phase 2 fire service shall be operational. 7/20/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 9/21/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No The broken door close button shall be repaired and properly marked. 11/22/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone shall work. The phone dials out, but could not establish two-way communication. 9/9/2024