Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x Emergency bell not working 9/29/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x Emergency light not working 9/29/2020
MO Minimum : Elevators (I) - Pits (I)1 Need to clean oily soaked pads out of pit 7/23/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current Sate certificate in machine room 8/27/2020
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) The machine room lighting has been changed to a motion type switch to activate. While this is an energy saving measure, it is also a safety code concern. Without motion, the switch deactivates the lighting, thereby leaving maintenance personnel with no lighting. Remove motion type switch to a conventional on/off switch.