ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
1/31/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
8/5/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO state operating certificate shall be posted in the elevator machine room.
|
11/11/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door.
|
8/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7.4 Protection of Light Bulbs and Tubes
|
|
|
Cab ceiling in pieces, unsecured, not properly guarding lamps and fan.
|
8/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.14 - Ventilation
|
2.14.2.3
|
|
|
Cab fan is not properly guarded from inside of cab.
|
8/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.5 - Access to Hoistway
|
8.11.2.1.4(e)
|
|
x
|
Hoistway access does not work properly. Elevator Red Tagged.
|
7/29/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11 Periodic Inspection and Test.
|
x
|
x
|
Independent service does not work properly. Elevator Red Tagged.
|
7/29/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
2.7.5.2
|
|
|
Machine room temperatures shall be kept within the manufacturers recommended temperature range.
|
4/6/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
2.7.5.2
|
|
|
Machine room temperatures shall be kept within the manufacturers recommended temperature range. Previously falsely marked compliant, still not working.
|
8/5/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
Machine Room: FAID/Shunt trip relay box cover is missing.
|
8/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide a code compliant MCP including on-site documents. No monthly fire service checklist.
|
4/6/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.42 Seismic (Earthquake protection)
|
8.4.10
|
x
|
|
Seismic/Ring & string does not work.
|
8/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11 Periodic Inspection and Test.
|
x
|
|
The full category 5 test and the full annual inspection still need to be completed.
|
9/2/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
12/7/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
7/29/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The machine room door shall have a code compliant lock.
|
11/11/2020
|
A17.1-2016 : Elevators
|
2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection
|
8.11.2.1.2(ii)
|
|
x
|
The rope gripper pads are excessively worn. Elevator Red Tagged.
|
7/29/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11 Periodic Inspection and Test.
|
x
|
|
There were several violations that were found that required the elevator to be red tagged while waiting for testing weights. The full category 5 test and the full annual inspection still need to be completed.
|
7/29/2021
|