Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Provide existing phone to work. 1/20/2026
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No Replace damaged phase II Fire recall operation signage 5/16/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Phase II Fire recall does not override the 3rd floor security. 1/12/2024
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes Repair no Phase II override of C.O.P. floor security key switches. Did not red tag. 4/10/2020
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes Repair Phase I audible buzzer. Did not red tag. 4/10/2020
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 No No Repair leak from under tank supply-side muffler. 1/23/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)12 (Door open zones) Yes No Door restrictor shall work. 11/19/2018