Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)2 Relief valve pressure setting at approximately full-load working pressure and below manufacturer's and previous job settings. Adjust relief valve. 1/23/2020
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)2 Relief pressure was observed at 300 psi, establish working pressure at 330psi. Provide code compliant minimum relief pressure, reinspect. 11/13/2020
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x 3rd floor security is not overridden during phase II Fire recall. 1/12/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Cylinder packing is worn and leaking, repair as needed. 5/16/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Cylinder packing worn and leaking, repair as needed. 5/16/2024
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Replace damaged Phase II fire recall signage 5/16/2024