MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)2
|
|
|
Relief valve pressure setting at approximately full-load working pressure and below manufacturer's and previous job settings. Adjust relief valve.
|
1/23/2020
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)2
|
|
|
Relief pressure was observed at 300 psi, establish working pressure at 330psi. Provide code compliant minimum relief pressure, reinspect.
|
11/13/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
3rd floor security is not overridden during phase II Fire recall.
|
1/12/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Cylinder packing is worn and leaking, repair as needed.
|
5/16/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Cylinder packing worn and leaking, repair as needed.
|
5/16/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Replace damaged Phase II fire recall signage
|
5/16/2024
|