Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion conversion - reinspect x Alarm bell in hatch does not work. 3/26/2019
conversion conversion conversion - reinspect x Install hoist rope anti-spin cable at car and counterweight. 3/26/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be posted in the elevator machine room. 8/7/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers A current tested ABC type fire extinguisher shall be provided in the elevator machine room. 8/7/2020
MO Minimum : Elevators (H) - Machine Rooms (H)8 The mainline disconnect wireway shall have a cover. 8/7/2020
MO Minimum : Elevators (H) - Machine Rooms (H)8 Generator wiring shall be enclosed in wireway or conduit. 8/7/2020
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) The machine room lighting shall be operational. 4/18/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers A current tested and tagged ABC type fire extinguisher shall be provided in the elevator machine room. 4/18/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 4/18/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing incomplete due to red tag of other elevator. Need to test: fire service, door pressure, cartop slack selector cable switch, light, bell, phone, pit, bottom door lock, weight portion of test (100% & 125%), slide, runby, pullout/pull-thru, gov electrical/mechanical. 12/18/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates COP shall have car number displayed (multiple units on-site).
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.