MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO state operating certificate shall be posted in the elevator machine room.
|
8/7/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
A current tested ABC type fire extinguisher shall be provided in the elevator machine room.
|
8/7/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
The mainline disconnect wireway shall have a cover.
|
8/7/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
Generator wiring shall be enclosed in wireway or conduit.
|
8/7/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
The machine room lighting shall be operational.
|
4/18/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
A current tested and tagged ABC type fire extinguisher shall be provided in the elevator machine room.
|
4/18/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
4/18/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
COP shall have car number displayed (multiple units on-site).
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Alarm bell in hatch does not work.
|
3/26/2019
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Install hoist rope anti-spin cable at car and counterweight.
|
3/26/2019
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Testing incomplete due to red tag of other elevator. Need to test: fire service, door pressure, cartop slack selector cable switch, light, bell, phone, pit, bottom door lock, weight portion of test (100% & 125%), slide, runby, pullout/pull-thru, gov electrical/mechanical.
|
12/18/2024
|