MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)11
|
|
|
Wedge rope socket is anchored incorrectly. When the steel wire rope has been seated in the wedge socket by the load on the rope, the wedge shall be visible, and at least two wire-rope retaining clips shall be provided to attach the termination side to the load-carrying side of the rope. The first clip shall be placed a maximum of 4 times the rope diameter above the socket, and the second clip shall be located within 8 times the rope diameter above the first clip.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean the pit of dirt and debris.
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Hoistway containing passenger elevators shall be fully enclosed and the enclosure shall be of solid construction to its full height. Enclose the 4 inch x 30 inch opening at the rear of the hoistway, between the basement and first floor landing.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
8.11.2.1.2(f)
|
|
|
The mechanical ventilation system in the machine room shall be operable.
|