Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone in car shall work 7/26/2023
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 Low oil pressure switch shall work. 8/27/2019
conversion conversion n/a 1) The level of oil in the oil tanks shall be checked and, where necessary, adjusted to comply with the prescribed minimum and maximum level. Oil level starting to pull air in pump during testing for relief pressure portion of testing. 8/27/2019