A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1001.2(d)12
|
x
|
|
Door did not close upon activation of Phase 1 fire service. Unit locked-off until repaired.
|
8/5/2019
|
A17.1-1996 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
102
|
|
|
102(c)(2) - Sprinkler branch lines in the hoistway shall supply sprinklers at not more than one floor level. Note: The sprinkler line enters the hoistway in the pit, supplying the sprinkler in the pit, then runs the entire length of the hoistway into the overhead, feeding the sprinkler in the overhead as well. Customer may need to apply for a variance.
|
9/13/2022
|
A17.1-1996 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
102
|
|
|
102(c)(2) - Sprinkler branch lines in the hoistway shall supply sprinklers at not more than one floor level. Note: The sprinkler line enters the hoistway in the pit, supplying the sprinkler in the pit, then runs the entire length of the hoistway into the overhead, feeding the sprinkler in the overhead as well. The school district is applying for a variance.
|
9/13/2022
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
The presence of an overspeed valve has been confirmed, along with an installation date of 2000. The overspeed valve shall be scheduled for the category 5 test required on or before the next annual inspection.
|
8/5/2024
|
A17.1-1996 : Elevators
|
1.8 - Door closing force
|
1001.2(a)(8)
|
x
|
|
Door closing force shall be tested once repairs are made to unit.
|
8/5/2019
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall work clearly. Answering service could hear person in elevator, but could not hear answering service in elevator.
|
8/3/2020
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
211.2
|
x
|
|
The auxiliary power lowering operation shall be functional.
|
8/12/2022
|