Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | Fire service phase 2 operation does not override security for basement car call. | 6/27/2018 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | x | Door reopening device is connected to car lighting circuit. Car lighting circuit shall be a dedicated circuit | 7/8/2021 |