Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | x | OSV failed to reset properly. Unit will be red tagged on 9/20/21 if not repaired or replaced and tested, sealed, and tagged | 5/24/2022 | |
A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | x | Perform OSV test. Noted on last inspection required 2021. Tag and seal upon completion. | 5/24/2022 |