MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone not working. Bldg line.
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Access to the Machine Deck not complete, Elev mod work prohibited the contrator from getting this work done.
|
8/24/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Enclosure of machine room must be completed.
|
8/24/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.6.4.11
|
x
|
|
Counterweight Runby is 3 inches minimum shall be 6 inches. Shorten Suspension Ropes must reinspect when work has been completed.
|
5/23/2025
|