Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 8/22/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator machine room. 9/15/2022
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Did not have the key to test the stop switch device in Phase 1. 8/4/2022
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 No No Machine Space shall have at least one(1) GFCI outlet. Currently no outlet available. Both positions take by building Cable modem and Elevator phone system.
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 8.10.2.2.2(r) No No Mainline disconnect while not return to the closed position normally. Locking device is faulty
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. 8/22/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No The in car emergency telephone shall be operational. 11/5/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No The MCP, including PM records and monthly fire service test log, are not being properly documented. 2/14/2024
MO Minimum : Elevators (I) - Pits (I)1 No No The pit shall be kept clean. 2/14/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) No No Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 8/22/2022