Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion conversion - reinspect x Telephone not working-no voltage on line to controller-reinspect required 6/15/2018
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) telephone not working--line voltage is low--second notice 6/19/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x Cannot use cab lighting to power door safety edge: NEC 620.22 11/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) Must Provide and Maintain all required MCP documentation and logs. 8.6.1.4.1 1/11/2023
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Must perform and document Monthly Fire Service test. 8.6.10.1 1/11/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Must post current state operating Cert. in the Mach room. 5.100(2) 1/11/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Car Lights and Fan must be a dedicated circuit. NEC 620.22 (Currently door safety edge is wired with Cab Light and fan) 1/11/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post updated certificate 1/11/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No maintenance records 1/11/2023
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Maintain mounthly log 1/11/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post updated certificate 1/11/2023