A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.8 Switch Keys
|
|
|
All fire service switches shall be FEOK1
|
10/22/2021
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
8.10.3.2.2(i)
|
x
|
|
NEC 620.5 working clearances 110.26(A) distance between controller and air conditioner note variance has been asked for
|
10/20/2020
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly
|
9/15/2022
|