A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone not working.
|
2/1/2019
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
x
|
|
Suspension ropes are below minimum diameter. Replace
|
3/31/2021
|
A17.1-1996 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
1206.8
|
x
|
|
Suspension ropes shall be shorten so that the elevator does not hit buffer while on the directional
|
1/25/2022
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.8 Switch Keys
|
x
|
|
Fire service switch keys for all elevators in one building shall be keyed alike. Re-inspection required
|
2/20/2024
|