A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
Yes
|
No
|
During phase 2 fire fighters operation the doors will not hold open. For elevators with power-operated doors, when the car is at a landing, with the doors open, and the “FIRE OPERATION” switch is in the “HOLD” position, the car shall remain at the landing with the doors open. The door close buttons shall be inoperative, and car calls shall not be registered.
|
6/13/2025
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
Yes
|
No
|
Various broken wires on governnor rope - replace
|
5/8/2019
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
No
|
No
|
The escape hatch safety switch plug will not seat back into the outlet without having to disassemble the whole mechanism. Replace the outlet.
|
|