Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No This inspection was stopped due to the 10th floor interlock problem, complete inspection shall be performed. 5/10/2023
MO Minimum : Elevators (A) - Hoistways (A)3 No No The top landing of this elevator is blocked off making it impossible to access the top of the elevator, means shall be put into place to remove the blockage of the top landing. If the blockage is not removed an alteration permit to access the elevator at a different top landing shall be obtained. If either or situations are not complied the elevator will be shut down.
MO Minimum : Elevators (A) - Hoistways (A)6 Yes Yes The 10th floor hoist way interlock shall be replaced or repaired so that the elevator will not run with doors open. This unit has been red tagged and requires reinspection 5/10/2023
MO Minimum : Elevators (F) - Electrical Switches (F)2 Yes Yes The final limit switch activates due to the leveling zone not being adjusted properly from non use. The leveling zone and the final limit switch shall be adjusted to not cause entrapment. The leveling zone shall be complaint to the Missouri Minimum Code section B12. 6/28/2022