ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The elevator ADA telephone inside the elevator is not working properly. Check and repair this phone for proper operation and passenger safety. Reinspection required.
|
7/19/2024
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required.
|
7/19/2024
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Reinspection required.
|
5/29/2018
|
conversion
|
conversion
|
n/a
|
|
|
The hoistway door interlock is out of adjustment and fails to allow the hoistway door to selfclose/ self-lock. The interlock mechanism shall be adjusted to self-close/self-lock as required.
|
2/7/2020
|
conversion
|
conversion
|
n/a
|
|
|
A hoistway door gib is missing on the 1st floor and shall be reinstalled into the door sill groove.
|
2/7/2020
|