Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage phase 2 in car sign missing
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) lights in mach room not guarded from breakage need sleeves on tubes
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements shorten comp chains 1 of 2 chains drag pit floor while traveling
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal Light on COP (Please Exit When Doors Open) not working 10/8/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Alarm bell needs to be replaced. Car does have a working phone 10/8/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Need Phase I and Phase II Fire service instructions 9/28/2022