MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
missing phase 1 & 2 signs for fireman operations
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)11
|
x
|
|
1 of 4 hoist ropes turn buckles is too short clips are not able to be spaced properly need to raise and re-clip correctly
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.3a(8) Visual and audible signal
|
|
|
Light on COP (Please exit car when doors open) needs bulbs.
|
10/8/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Need Phase II Fire service instructions
|
9/28/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Phase I and Phase II Fire service instructions need to be replaced.
|
9/28/2022
|