Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation Test and log firefighter operation monthly 11/10/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state operating certificate inside machine room 11/10/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The current State Operating Certificate not displayed or on site because owner didn't signoff on violation correction form. 11/10/2021
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.2-211.8 x x Building Fire System Control System-Lightning Struck System down with no protection for the Elevator. Red Tagged & Must Retest all initiating devices prior to Red Tag being removed. 12/12/2022
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.3a(8) Visual and audible signal x Per 211.3(b)(5) Fire Hat Visual is not functioning correctly must Re-inspect when issue has been corrected. 11/16/2023