Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service (S)1 x x "HOLD" doesn't work on Phase II fire service. 4/22/2020
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV shall be tested on or before next annual inspection. 8/10/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Electric door reopening sensor does not reopen the door when an object crosses the threshold 2/13/2024