Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x Car door restrictor shall work at all floors. There are parts missing.
conversion conversion n/a Door will not stay open on Phase II operation 7/11/2018
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 Fire service testing must be documented monthly.
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting Machine room lighting needs to be repaired. One or more bulbs are not working.
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV is not sealed. Perform OSV test on or before next annual inspection.
conversion conversion n/a Repair door Restrictor 7/11/2018
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work properly. Agent said it sounded "extremely faint" and inspector had to repeat everything multiple times to be understood.