Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x emg phone not working no answer 12/19/2024
A17.1-2016 : Elevators 2.17 - Drive machine brake 8.6.4.19.11 Ascending Overspeed Protection, Unintended Movement Devices, and Emg Brake x not able to test rope gripper not working
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.13.1(l)(Door Restrictor) x door restrictor has been removed
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.1 - Car platform guard 2.15.9 when elevator has rope gripper 48'' platform guard reguired
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.1 - Car platform guard 2.15.9 toe guard less than 48 ins.unit has rope gripper
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.5 Phase 1 Visual Signal (Re-Inspection) x fire serv. hat at phase one station not lighting
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate no current cirt displayed
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records no maint records on site
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) lighting over controller not working
MO Minimum : Elevators (F) - Electrical Switches (F)2 x The upper and lower final limit swithes are not working 7/20/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate no current cirt posted 8/20/2024