Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a New hoistway penetrations shall be sealed (at the top floor). 6/21/2019
conversion conversion n/a Wiring not related to the elevator shall not be added to the hoistway (at the top floor). 6/21/2019
conversion conversion n/a A 2nd heat detector is required withing 24" of the second fire sprinkler head in hoistway overhead. 6/21/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements 2.2.3 - Safety screen mesh shall be installed between two hoistways. Passenger hydraulic on backside of freight car shall have a divider.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Up to date operating certificate is required in the machine room.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators (H) - Machine Rooms (H)4 Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The in-car emergency light shall be operational.
MO Minimum : Elevators (H) - Machine Rooms (H)2 x Some of the machine room walls have been torn down and are missing. It's currently open and without a door. The elevator machine and control equipment shall be located in a separate room or separated space designed as an elevator machine room or space and shall be accessible only to authorized personnel.
MO Minimum : Elevators (H) - Machine Rooms (H)2 x All rooms or enclosures shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key.