Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)4 Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. 3/11/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Up to date operating certificate is required in the machine room. 3/11/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 3/11/2026
MO Minimum : Elevators (F) - Electrical Switches (F)2 x The final limit needs to be adjusted or the cables need to be shortened. The final limit switch opens just as the counterweight strikes the spring buffer and sometimes will make back up due to the buffer spring bouncing the car back down. Currently there is 6 3/4" of counterweight runby. 7/10/2025
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x Car governor jaw does not grab rope and set safeties when activated
MO Minimum : Elevators (I) - Pits (I)4 x x Counterweight is on the springs before car reached final limit swith. It must have a minimum of a 6" runby.
MO Minimum : Elevators (F) - Electrical Switches (F)2 x x Bottom final limit does not work when activated.
MO Minimum : Elevators (S) - Fire Service (S)1 x x Fire service jewel does not work when car is on fire service.