MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)2
|
x
|
|
The final limit needs to be adjusted or the cables need to be shortened. The final limit switch opens just as the counterweight strikes the spring buffer and sometimes will make back up due to the buffer spring bouncing the car back down. Currently there is 6 3/4" of counterweight runby.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Up to date operating certificate is required in the machine room.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|