Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted near the equipment, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Emergency power operation shall be tested.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Emergency/standby power shall be tested. Note: The unit has an indicator light and key-switch for emergency power. Building personnel were unsure if this unit is served by a generator in the case of a grid failure. If it is, it shall be tested. If it isn't, the related fixture shall be removed. 3/15/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The emergency/standby power shall be tested. 3/24/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an overspeed valve that in not sealed. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test.
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x When the hall fire recall key-switch is in the "ON" position, or an initiation device has been activated, a stopped car shall have the in-car stop switch rendered inoperative as soon as the car moves away from the landing. A moving car shall have the switch rendered inoperative without delay. Note: The acceptance tests were witnessed by St. Louis County last month. The code data plate is marked for compliance with A17.1-2013, as required by St. Louis County. A17.1-2013 requires the switch to be rendered inoperative. A17.1-2016 (the current MO State code) does not. 3/15/2023
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.6(c) Stop Switch Inoperable in Fire Service (Re-Inspection) x When the hall fire recall key-switch is in the "ON" position, or an initiation device has been activated, a stopped car shall have the in-car stop switch rendered inoperative as soon as the car moves away from the landing. A moving car shall have the switch rendered inoperative without delay. Note: The acceptance tests were witnessed by St. Louis County last month. The code data plate is marked for compliance with A17.1-2013, as required by St. Louis County. A17.1-2013 requires the switch to be rendered inoperative. A17.1-2016 (the current MO State code) does not. This violation was originally cited in 2022 and has not been addressed. Customer to apply for a variance from the State of Missouri to clear violation. 5/28/2024