MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
1.5 emergency light needs battery
|
9/9/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
cab light needs cover for protection
|
9/9/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.2 Replacement of Suspension Means (Re-Inspection)
|
x
|
|
car is roped 2-1 with the cwt sheave having 1 of 4 rope grooves damaged by tension. needs to undercut or replace
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
emergency light needs battery
|
9/9/2020
|
conversion
|
conversion
|
n/a
|
|
|
Emergency light needs repaired
|
11/8/2018
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency lights not working
|
9/29/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.11 Runby (Re-Inspection)
|
x
|
|
Hoist ropes need to be shortened to provide minimum 6" runby clearance at counterweight buffer.
|
9/17/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Need Phase I and Phase II Fire service instructions placed by each key switch
|
9/29/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
phase 2 sign in cab missing
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.11 Runby (Re-Inspection)
|
x
|
|
Ropes need to be shortenee
|
9/29/2022
|