Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide written maintenance control program on site for each elevator. 9/23/2022
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Repair inoperative pit light 9/23/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace damaged guide roller on elevator car top 10/29/2024
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x During the full load car safety test, the car racked (out of level by 3 inches) and pulled the top right guide rollers off the guide rail. Repair the car safeties and perform full load car safety test. Elevator was Red-tagged and removed from service. Re-inspection required 10/24/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to perform counterweight buffer test at rated speed with no load. Re-inspection required 10/24/2023
A17.1-1996 : Elevators 1.8 - Door closing force 1001.2(a)(8) x Door Restrictor shall be adjusted 2/25/2019