A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A written maintenance control program shall be kept on site for each elevator.
|
9/23/2022
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
x
|
|
Car door restrictor does not work. Re-inspection required
|
11/18/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Category 5 test is incomplete, need to perform the following tests: Car buffer at rated speed with rated load, Counterweight buffer at rated speed with no load, Car safeties at rated speed with rated load, machine brake with 125% of rated load. Re-inspection required in 30 days
|
2/9/2024
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Close hole in the pit wall around the sump pump discharge
|
9/23/2022
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
Elevator cab emergency lights do not work. Re-inspection required
|
11/18/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone in elevator cab does not work, needs repaired. Re-inspection required
|
2/9/2024
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1001.2(b)(5)
|
|
|
Remove condensate water from machine room floor
|
9/23/2022
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Repair inoperative pit light
|
9/23/2022
|