Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A written maintenance control program shall be kept on site for each elevator. 9/23/2022
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x Car door restrictor does not work. Re-inspection required 11/18/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Category 5 test is incomplete, need to perform the following tests: Car buffer at rated speed with rated load, Counterweight buffer at rated speed with no load, Car safeties at rated speed with rated load, machine brake with 125% of rated load. Re-inspection required in 30 days 2/9/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Close hole in the pit wall around the sump pump discharge 9/23/2022
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Elevator cab emergency lights do not work. Re-inspection required 11/18/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Phone in elevator cab does not work, needs repaired. Re-inspection required 2/9/2024
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) Remove condensate water from machine room floor 9/23/2022
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Repair inoperative pit light 9/23/2022