conversion
|
conversion
|
n/a
|
|
|
The elevator machine room cannot be used for storage. Remove the items (old AC units) being stored in the machine room to provide proper room for maintenance to be performed.
|
7/10/2018
|
conversion
|
conversion
|
n/a
|
|
|
The fire extinguisher in the machine room needs to be serviced, the last annual service tag indicates it was serviced in 2016.
|
7/10/2018
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
The anti-rotation cable on the car side suspension shackles is frayed and coming apart. Replace the anti-rotation cable.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Provide a governor rope data tag
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Inspection incomplete. Need to test pullout/pull through, set the safeties with a full load, fire service, 110 back up power, counter weight buffer, and emergency phone
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone line does not work
|
3/25/2025
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.2 Replacement of Suspension Means (Re-Inspection)
|
x
|
x
|
Suspension ropes are showing rouge and the diameter has reduced beyond the maximum allowable amount. Replace suspension ropes.
|
|
A17.1-2016 : Elevators
|
2.13 - Governor, Overspeed Switch, and Seal
|
8.6.4.20.2
|
x
|
x
|
The pullout is higher than the pull through of the governor. The safetiies releasing carrier does not pull out when the jaw is fully set.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
When a car is outside the unlocking zone, the car doors shall be so arranged that when in the closed position they shall be restricted from opening
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.2.5 Rope Tension (Re-Inspect)
|
x
|
|
Replace the broken springs located on the suspension rope shackles and tension the ropes
|
|