Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone in elevator cab does not work.
A17.1-1996 : Elevators 3.28 - Counterweight and counterweight buffer 1001.2(c)(13) x The bottom guide rollers on the counterweight are deteriorated and shall be replaced. 4/20/2021
A17.1-2016 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 8.11.2.1.5(c) x Replace rollers on traveling buffer counterweight assembly.
conversion conversion n/a The elevator machine room cannot be used for storage. Remove the items (old AC units) being stored in the machine room to provide proper room for maintenance to be performed. 9/11/2018
conversion conversion n/a The fire extinguisher in the machine room needs to be serviced, the last annual service tag indicates it was serviced in 2016. 9/11/2018
conversion conversion conversion - reinspect x The fireman's emergency service phase I and II operations was tested and the following deficiency was noted:The visual signal device did not light in the car when phase I was activated. Reinspection is required. 9/11/2018
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current operating certificate in machine room.