Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Elevator machine room lighting is less than 10 foot candles and shall be repaired to have proper lighting 10/14/2022
MO Minimum : Elevators (H) - Machine Rooms (H)4 Machine room appears to have a crack in the ceiling and it is leaking causing water to drip next to a light outlet and down onto the floor next to the governor. Repair ceiling and clean floor 10/14/2022
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Elevator pit light shall be a minimum of 5 foot candles and it does not work. Repair or replace 10/14/2022
MO Minimum : Elevators (I) - Pits (I)8 Pit sump hole is not covered and shall have proper grating coverage 10/14/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements The elevator has a phase 2 fire service key switch inside the elevator and the elevator appears to not have phase 2 fire service. The key switch shall be removed
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x The in car emergency telephone shall be operational. 1/18/2021