Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)7 x The force necessary to prevent closing of the car door from rest shall not exceed 30 lbs. 8/5/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Provide MCP and wiring diagrams. 7/25/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements MCP & electrical wiring diagrams shall be kept on-site. 7/25/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x The relief pressure shall be tested. 6/11/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x There were no fire service keys on-site to test Phase 1 operation. Keys shall be available on-site and Phase 1 fire service shall be tested to complete the inspection. 8/5/2021