Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)14 All elevators provided with automatic leveling where the landing sills project within the hoistway, shall be equipped with a bevel on the underside of the landing sill meeting the requirements of CSR 40-5.065 (A)14. Note: This elevator has no fascia between the top and bottom landings. It also isn't equipped with a door restrictor (not required under Missouri Minimums) which could present a hazardous condition with the car door open between floors and a substantial gap between the car sill and the hoistway wall. A bevel is required, but I recommend installing fascia from the bottom floor header to the top floor sill to close the gap. 9/23/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x In car emergency telephone shall work. 8/5/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x There were no keys on-site to test fire service. Keys shall be kept on-site and Phase 1 fire service shall be tested. 8/5/2021