A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.4
|
x
|
|
Pit ladder needs to be installed.
|
10/22/2024
|
A17.1-2016 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
2.4.1.6
|
x
|
|
Refuge space shall be marked on the pit floor.
|
10/22/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
x
|
|
Distance of counterweight shackles to deflector sheave when car is on compressed buffer is insufficient. Repair as needed.
|
10/22/2024
|
A17.1-2016 : Elevators
|
4.2 - Hoistway doors
|
8.6.4.13 Door Systems
|
x
|
|
Door safety retainers shall be installed on bottom of hoistway doors.
|
10/22/2024
|