Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(c) On-Site Maintenance Records (Other Records) A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room. 8/18/2023
MO Minimum : Elevators (I) - Pits (I)1 clean up the pit, hydraulic oil all over the pit floor 8/6/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate display the current copy of the state operating certificate in the elevator machine room and update it annually when received from the state, the certificate in the machine room expired in 2015 8/18/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display the current copy of the state operating certificate in the machine room, the one in the certificate frame expired in 2015 10/10/2024
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log monthly fire service test log was not posted in the machine room 8/6/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance packing gland is leaking excessively, 5 gallon pit bucket overflows between maintenance visits, install new packing gland 8/6/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates the crosshead data plate has the capacity as 2100, the car operating panel has the capacity as 2500, the capacity on the data tag on the tank in the machine room is 2500. put the correct capacity of 2500 on the crosshead data tag 8/18/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.11.1 Firefighters' Emergency Operation & Documentation The Monthly fire service test log in the machine room is not being filled out does not have any entries for 2024 on the log 10/10/2024