Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency light and alarm bell are not working. 4/2/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency light and alarm bell do not work. 3/25/2021
MO Minimum : Elevators (I) - Pits (I)1 Remove water from pit.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x The car door restrictor device shall be repaired so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Currently, the battery backup system for the door restrictor is not operating correctly which is resulting in a nuisance alarm sounding continuously. Reinspection is required. 4/21/2023
MO Minimum : Elevators (I) - Pits (I)1 The elevator pit floor is covered in water. The elevator pit shall be kept clean and dry. Sealing of the pit or some sort of water containment/diversion channel shall be constructed.
MO Minimum : Elevators (I) - Pits (I)8 The sump pump hole in the pit shall be provided with a noncombustible cover that is flush with the pit floor. There is currently no cover provided.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x The elevator alarm bell inside the elevator is not working. Check and repair the alarm bell for proper operation and passenger safety. 4/21/2023
MO Minimum : Elevators (I) - Pits (I)8 The sump pump hole in the pit shall be provided with a non combustible cover that is flush with the pit floor. There is currently no cover provided 5/10/2023
MO Minimum : Elevators (I) - Pits (I)1 Provide means to keep pit floor dry (water).
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance x Car failed 15 minute stand test. Tech determined that it was going back through the valve, repair as needed, retest.