Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.7 Record of Oil Usage x x car failed set test after relief valve test Oil is seen leaking from cylinder at floor level RED TAG
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone not working 11/19/2021
MO Minimum : Elevators (H) - Machine Rooms (H)4 Janitorial equipment stored in machine room
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door has self-closer but door is tight in jamb and must be pulled shut.
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door must be self-locking
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x no working phone line
MO Minimum : Elevators (I) - Pits (I)1 Pit has water. Sump pump not working.
MO Minimum : Elevators (I) - Pits (I)8 sump hole cover missing