Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) 1.5 emergency light needs battery 6/6/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements 1004.2(27)(e)(3) piston dragging on cylinder wall needs realigned 6/6/2019
MO Minimum : Elevators (S) - Fire Service (S)1 x Phase II will not override key lockouts on car buttons 8/23/2018
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x ANSI ASME A17.1 2.8.3.3.4 requiresThe Sprinkler in the pit shall be 24 inches from pit floor and all the Electrical Equipment below 48 inches shall be waterproof NEMA 4 as specified in NEMA 250. 8/8/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 x NEC Elevator Main Disconnect is not Readily Accessible in an Emergency situation. The machine room is small and the machine room entry door because it opens into the room the entry door must be closed to reach the Main Line Disconnect. Reversing the entry process would eliminate this potential Hazard. 8/8/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post updated certificate 5/24/2022