MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
|
|
1.5 emergency light needs battery
|
6/6/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
1004.2(27)(e)(3) piston dragging on cylinder wall needs realigned
|
6/6/2019
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
ANSI ASME A17.1 2.8.3.3.4 requiresThe Sprinkler in the pit shall be 24 inches from pit floor and all the Electrical Equipment below 48 inches shall be waterproof NEMA 4 as specified in NEMA 250.
|
8/8/2024
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
x
|
|
NEC Elevator Main Disconnect is not Readily Accessible in an Emergency situation. The machine room is small and the machine room entry door because it opens into the room the entry door must be closed to reach the Main Line Disconnect. Reversing the entry process would eliminate this potential Hazard.
|
8/8/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Phase II will not override key lockouts on car buttons
|
8/23/2018
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post updated certificate
|
5/24/2022
|