Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)4 Articles or material not necessary for the operation of the elevator shall not be stored in the Elevator Machine Room. 7/25/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.6 Sump Pump Covers x Sump cover to be relatively flush with floor.
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 x Pit lighting shall not be less than 10fc.
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone does not connect.
A17.1-2016 : Elevators 2.4 - Machine space 2.7.1 x Fire caulk around conduit penetrations, replace damaged ceiling tiles in machine room.
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x Install outlet/switch covers.
A17.1-2016 : Elevators 3.10 - Hoistway construction 3.1 x Fire caulk hoistway and pit fire penetrations.
A17.1-2016 : Elevators 5.11 - Plunger and Cylinder 3.18.3.3 x Jack/cylinder does not allow full compression of buffer springs before cylinder bottoms out in jack.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 3.27.1 Phase I Emergency Recall Operation After Device Actuation x x 2nd and 3rd floor devices not permanently installed (ceilings not installed, devices hanging by their wiring).
A17.1-2016 : Elevators 5.12 - Car Buffer 3.6.3 x Buffer spring height does not allow for minimum overtravel of 3.75".
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.